SSR-12 Environmentally Friendly Gas Insulated Ring Network Switchgear

image086

The SSR-12 environmentally friendly gas-insulated ring panel does not run the risk of insulation failure as SF6 switches do when the air pressure gradually decreases at low temperatures.

image087

The greenhouse effect gas SF6 is canceled, and all materials are non-toxic and harmless environmental protection materials.

image095

SSR-12 Environmental Gas Insulated Ring Network Cabinet

· SSR-12 environmental protection gas insulated ring network cabinet is a digital ring network cabinet with environmental protection materials, full insulation, full airtight, economical price and convenient operation.

· All the conductive parts in the switch are installed in a sealed stainless steel gas box, and the dry air is used as the insulating body in the gas box; the main switch adopts vacuum arc extinguishing, and the isolating switch adopts a three-station structure.

· The adjacent cabinets are connected by solid insulated busbars.

· The secondary circuit adopts integrated control technology and supports data transmission function.。

Cabinet structure

Top and bottom isolated symmetrical design

The upper isolation and the lower isolation adopt a symmetrical design scheme, and all parts required for the operating mechanism and switch are common, which shortens the manufacturing cycle and facilitates quality management. Adjacent cabinets are connected by side expansion/top expansion.

Cable Warehouse

- The cable compartment can only be opened if the feeder has been isolated or grounded.
- The bushing complies with DIN EN 50181, M16 bolt connection.
- The lightning arrester can be attached to the back of the T-cable head.
- The one-piece CT is located on the side of the bushing for Easy installation of the cable and is not affected by external forces.
- The height from the casing installation to the ground is Greater than 650 mm.

Pressure relief channel

If an internal arc fault occurs, the special pressure relief device installed in the lower part of the cabinet will automatically open for pressure relief.

image191

Circuit breaker unit - core component (upper isolation)

image141

Isolation mechanism

Single spring double operation shaft design, built-in reliable closing, opening, grounding limit interlocking device, to ensure that there is no obvious overshoot phenomenon of closing and opening. The mechanical life of the product is more than 10,000 times, and the electrical components are designed in front, which can be installed and maintained at any time.

image142

Breaker mechanism  

The precision transmission mechanism with reclosing function adopts V-shaped key connection, and the shaft system support of the transmission system adopts a large number of rolling bearing design schemes, which are flexible in rotation and high in transmission efficiency, thus ensuring the mechanical life of the product for more than 10,000 times. Can be installed and maintained at any time.

image143

Arc extinguishing device and isolating switch

Adopting cam structure of closing and dividing device, with precise size of over travel and full travel, and strong production compatibility. Insulation side plate adopts SMC molding process, with precise size and high insulation strength. The isolation switch adopts three-position design for closing, dividing and grounding, which is safe and reliable.

image137

Circuit breaker unit - core

image103

Breaker mechanism     

The precision transmission mechanism with reclosing function adopts V-shaped key connection, and the shaft system support of the transmission system adopts a large number of rolling bearing design schemes, which are flexible in rotation and high in transmission efficiency, thus ensuring the mechanical life of the product for more than 10,000 times. Can be installed and maintained at any time.

image104

Isolation mechanism

Single spring double operation axis design, built-in reliable closing, breaking, grounding limit interlocking device, to ensure that the closing and breaking without obvious overshoot phenomenon. The mechanical life of the product is more than 10,000 times, and the front design of the electrical components can be retrofitted and maintained at any time.

image105

Arc extinguishing devices and disconnect switches

The closing and opening device with cam structure has precise over-travel and full-stroke dimensions, and strong production versatility. The insulating side plate adopts SMC molding process, with precise size and high insulation strength.

The closing, opening and grounding of the isolating switch adopt a three-position design, which is safe and reliable.

image137

Isolation switch core components

image099

Three-station isolation mechanism

Single spring double operation axis design, built-in reliable closing, breaking, grounding limit interlocking device, to ensure that the closing no obvious overshoot phenomenon. Product mechanical life More than 10,000 times, electrical components front design, can be added and maintained at any time. The front design of electrical components can be retrofitted and maintained at any time.

image136

Three-station isolation mechanism

The isolating switch adopts a three-position design to prevent misoperation. The high-performance disc spring ensures the stability of the contact pressure and is conducive to the design of the contact shape of the closing shape, thereby ensuring the reliability of the grounding and closing.

image137

Solid Insulated Switches

image131
image166

The customer only needs to install the core unit module in the cabinet as a set.

image165

We provide customers with a full range of free cabinet drawings, secondary schematic drawings, product manuals, promotional materials, technical advice and other services.

image164

The core unit module can be sold separately to the public, and all parameters have been adjusted in place before leaving the factory, so customers do not need to debug again.

User-friendly human-machine interface

① The analog busbar is clear and easy to operate.

② The main switch is made of alloy button, easy   to operate and avoid aging.

③ The grounding switch is equipped with a "voltage blocking device" to prevent the grounding switch from being closed by mistake with electricity.

④ The isolation and grounding switches have two separate operation holes to avoid misoperation.

⑤ Operation hole with anti-misoperation cover and pad lockable.

⑥  Wide angle lens with its own illumination system for easy observation of the isolation break.

image109

Operating parameters

image092